Product description
♦AC grid transducer converts an an voltage or current input into a load independent output signal
♦With excellent temperature characteristic and good working stability
♦The unit conforms to IEC 60688.
In a addition it meets as the high frequency disturbance test of IEC 60255-22 for Class III test voltage
Accuracy Measurement |
|
Accuracy Measurement |
Class 0.5,0.2 |
Input measurement |
|
Rated value |
Current : AC 1A,DC 5A |
Voltage:AC,DC 100V,300V,500V |
|
Overload |
1.2times (continuous) |
Voltage:2 times/1(instantaneous),Current :10times/5(instantaneous) |
|
Absorbed power |
Current input≤0.3VA; |
Voltage input ≤0.3VA(100Vh) ≤0.6VA(300Vh), ≤VA(500Vh) |
|
Frequency |
50±5Hz,60±5Hz |
Output |
|
Rated value |
4-20mA,0-20mA,4-12-20mA,0-5V,0-10V |
Load resistance |
Current signal output ≤600Ω,voltage signal output≥1000Ω |
Wave content |
<0.5%peak |
Response times |
|
Response times |
≥400ms |
Power supply |
|
Voltage |
AC110/220V± 15%;AC ,DC85-270V |
Power consumption |
AC Voltage and Current ≤3VA ,power ≤4VA |
Insulation resistance |
≥100mΩ |
With stand intensity |
2.0kV/1 min,50HZ |
Temperature coefficient |
≤100ppm/℃ |
Environment |
|
Temperature |
Operation:-25~+55℃;storage:-25~+70℃ |
Alititude |
≤2000m |
Install |
Ts35 guide way or fixed on switch cabinet by bolts |